Title :
Process identifier and its application to industrial control
Author :
Crowe, J. ; Johnson, M.A.
Author_Institution :
Roche Products Ltd., Dalry, UK
fDate :
3/1/2000 12:00:00 AM
Abstract :
Many industrial controllers use the relay experiment to estimate the system ultimate data for three-term controller tuning. However, for some systems the relay experiment describing function analysis can produce poor estimates. The paper reports a new and more accurate method of finding system frequency response data including the system ultimate data. A full demonstration of the accuracy attainable by the new method is presented. The new method was motivated by a phase-locked loop concept. The additional flexibility to find gain and phase margins, or the peak resonance frequency is demonstrated. The paper includes the application of the module to closed-loop system identification and a brief discussion of the LabVIEW implementation
Keywords :
frequency response; identification; phase locked loops; process control; relay control; three-term control; tuning; LabVIEW; gain margins; industrial controllers; peak resonance frequency; phase margins; phase-locked loop concept; process identifier; three-term controller tuning; ultimate data;
Journal_Title :
Control Theory and Applications, IEE Proceedings -
DOI :
10.1049/ip-cta:20000131