DocumentCode :
1339057
Title :
Study of influence of buried metallic structures on soil resistivity measurements
Author :
Ma, J. ; Dawalibi, F.P.
Author_Institution :
Safe Eng. Services & Technol. Ltd., Montreal, Que., Canada
Volume :
13
Issue :
2
fYear :
1998
fDate :
4/1/1998 12:00:00 AM
Firstpage :
356
Lastpage :
365
Abstract :
A detailed study of the influence of buried metallic structures on soil resistivity measurements has been carried out. Different measurement methods, various soil structures, and different locations of measurement profiles with respect to metallic structures have been analyzed. It is found that the influence of buried metallic structures on soil resistivity measurements can be significant and that this influence varies in a wide range depending on measurement methods, locations of measurement profiles and soil structure characteristics. This study also shows how to choose measurement locations to minimize the influence of buried metallic structures when soil resistivity measurements must be made in the presence of buried metallic structures
Keywords :
earthing; electrical conductivity measurement; soil; Schlumberger method; Wenner method; buried metallic structures influence; grounding; measurement methods; measurement profiles locations; multilayer soil; soil resistivity measurements; soil structures; transmission line right-of-way; two-layer soil; uniform soil; Algorithm design and analysis; Computational modeling; Conductivity measurement; Grounding; Impedance measurement; Nonhomogeneous media; Poles and towers; Probes; Soil measurements; Transmission line measurements;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.660902
Filename :
660902
Link To Document :
بازگشت