• DocumentCode
    1344516
  • Title

    Triggered-vacuum switch-based fault-current limiter

  • Author

    Jing, Shi ; Jiyan, Zou ; Junjia, He

  • Author_Institution
    Dept. of Electr. Eng., Huazhong Univ. of Sci. & Technol., Hubei, China
  • Volume
    20
  • Issue
    6
  • fYear
    2000
  • fDate
    6/1/2000 12:00:00 AM
  • Firstpage
    51
  • Lastpage
    53
  • Abstract
    A new fault current limiter (FCL) is proposed based on triggered vacuum switch (TVS). The TVS-based FCL (TFCL) is mainly composed of a capacitor, a current-limiting reactor connected with the capacitor in series and a TVS connected with the capacitor in parallel. With the TVS in the off or on state, the whole TFCL behaves as a conventional series compensation or fault current limitation, respectively. Compared with other types of FCL, such as superconductivity, thyristor/GTO-based FCL, TFCL demonstrates distinguished characteristics, such as high capacity, loss free, and low price. The digital simulation and prototype experiment based on LC resonant test circuit show that it is feasible to develop TFCL
  • Keywords
    capacitors; fault current limiters; vacuum switches; LC resonant test circuit; capacitor; current-limiting reactor; digital simulation; fault-current limiter; high capacity; loss free; low price; series compensation; triggered-vacuum switch; Capacitors; Circuit faults; Circuit testing; Digital simulation; Fault current limiters; Fault currents; Inductors; Superconductivity; Switches; Thyristors;
  • fLanguage
    English
  • Journal_Title
    Power Engineering Review, IEEE
  • Publisher
    ieee
  • ISSN
    0272-1724
  • Type

    jour

  • DOI
    10.1109/39.846112
  • Filename
    846112