• DocumentCode
    135228
  • Title

    Modified z-source DC circuit breaker topologies

  • Author

    Overstreet, Allan ; Maqsood, Atif ; Corzine, K.

  • Author_Institution
    Dept. of Electr. & Comput. Eng., Clemson Univ., Clemson, SC, USA
  • fYear
    2014
  • fDate
    11-14 March 2014
  • Firstpage
    1
  • Lastpage
    6
  • Abstract
    The z-source breaker has been introduced as a new circuit for quickly and automatically switching off in response to faults. A modified z-source breaker design is introduced for operation at medium-voltage dc with future applications in naval ship power systems. Compared to existing designs the respective design will allow for step changes in load. This new design also limits capacitor current in the circuit and can be easily modified for fault detection. Analysis of the breaker operation is presented during both fault and step changes in load. Low voltage laboratory validation of the breaker was carried out on two different versions of the proposed circuit.
  • Keywords
    capacitors; circuit breakers; fault diagnosis; topology; automatically switching; capacitor current; fault detection; low voltage laboratory validation; medium-voltage dc; naval ship power systems; z-source DC circuit breaker topologies; Capacitors; Circuit faults; Load modeling; Resistors; Steady-state; Thyristors; Transient analysis; Circuit breakers; Medium Voltage DC; Power system protection; RLC circuits; Thyristors circuits;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power Systems Conference (PSC), 2014 Clemson University
  • Conference_Location
    Clemson, SC
  • Type

    conf

  • DOI
    10.1109/PSC.2014.6808121
  • Filename
    6808121