DocumentCode :
135274
Title :
Improved superimposed current phase selector of wind farm with crowbar system
Author :
Tao Huang ; Yuping Lu
Author_Institution :
Sch. of Electr. Eng., Southeast Univ., Nanjing, China
fYear :
2014
fDate :
27-31 July 2014
Firstpage :
1
Lastpage :
5
Abstract :
Superimposed current phase selector (SCPS) is commonly used in transmission line protection, but it is affected by the distinction between positive and negative sequence impedances. However, this problem becomes more pronounced when it used in wind farm. In this paper, performance of SCPS is analyzed first considering the wind farm with crowbar system. It is exposed that amplitude and angle of wind farm positive and negative sequence impedances will differ significantly when crowbar system is activated, which could possibly paralyzes SCPS. Then an improved phase selection scheme is proposed, and the superimposed current is compensated by positive sequence fault current to eliminate impedances difference. Finally, simulation is performed to support the proposed scheme.
Keywords :
fault currents; power transmission faults; power transmission lines; power transmission protection; wind power plants; SCPS; crowbar system; impedance difference elimination; positive sequence fault current; sequence impedance; superimposed current phase selector; transmission line protection; wind farm; Circuit faults; Fault currents; Impedance; Relays; Resistance; Rotors; Wind farms; crowbar; positive and negative sequence impedances; positive sequence fault current compensation; superimposed current phase selector;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
PES General Meeting | Conference & Exposition, 2014 IEEE
Conference_Location :
National Harbor, MD
Type :
conf
DOI :
10.1109/PESGM.2014.6939217
Filename :
6939217
Link To Document :
بازگشت