DocumentCode :
1358073
Title :
Upgrading the protection of industrial-sized generators using digital technology
Author :
Mozina, Charles J.
Author_Institution :
Beckwith Electr. Co. Inc., Largo, FL, USA
Volume :
33
Issue :
4
fYear :
1997
Firstpage :
1117
Lastpage :
1123
Abstract :
This paper presents the reasons why industrial generator owners should consider upgrading the electrical protection of their generators to meet today´s standards. It specifically outlines the risks assumed in five functional areas where 20+-year-old generator protection is inadequate. These areas include negative sequence (unbalanced current) protection, sensitive stator ground-fault protection, sensitive overexcitation protection, inadvertent (accidental) generator energizing, and VT fuse loss protection. It also outlines the need to provide generator oscillographic monitoring. The paper discusses the advantages of digital versus conventional technology for such an upgrade program
Keywords :
earthing; electric generators; electrical faults; machine protection; maintenance engineering; stators; accidental generator energizing; digital technology; industrial-sized generator protection; negative sequence protection; oscillographic monitoring; sensitive overexcitation protection; sensitive stator ground-fault protection; standards; unbalanced current protection; upgrade guidelines; voltage transformer fuse loss protection; Circuits; Costs; Fuses; Industry Applications Society; Paper technology; Power generation; Power system protection; Reluctance generators; Rotors; Stators;
fLanguage :
English
Journal_Title :
Industry Applications, IEEE Transactions on
Publisher :
ieee
ISSN :
0093-9994
Type :
jour
DOI :
10.1109/28.605756
Filename :
605756
Link To Document :
بازگشت