    A new approach to islanding detection of dispersed generators with self-commutated static power converters

  • Author

    Huang, Shyh-Jier ; Pai, Fu-Sheng

  • Author_Institution
    Dept. of Electr. Eng., Nat. Cheng Kung Univ., Tainan, Taiwan
  • Volume
    15
  • Issue
    2
  • fYear
    2000
  • fDate
    4/1/2000 12:00:00 AM
  • Firstpage
    500
  • Lastpage
    507
  • Abstract
    In this paper, an islanding detection approach for dispersed generators with a self-commutated static power converter is proposed. This method is suggested based on the monitoring of the magnitude and sign change in ∂fB/|∂PL. To facilitate the detection process, a designated circuit for generating the output power deviation is also developed. The proposed method has been tested under various scenarios in order to examine the detection performance and operation reliability. It is found that the proposed method effectively detects the islanding event when different amount of power mismatch is considered. Moreover, by employing the simulated disturbances to the test system, the outcome reveals that the probability of false alarm is low. Test results solidify the feasibility of the method for the application considered
  • Keywords
    commutation; power convertors; power generation faults; power system analysis computing; power system stability; computer simulation; detection performance; dispersed generators; false alarm probability; islanding detection approach; operation reliability; output power deviation; power mismatch; self-commutated static power converters; simulated disturbances; Circuits; Condition monitoring; Distributed power generation; Frequency; Power generation; Power system protection; Power system relaying; Process design; Protective relaying; Static power converters;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.852975
  • Filename
    852975