DocumentCode :
1361117
Title :
Comparison of performance indices for detection of proximity to voltage collapse
Author :
Cañizares, Claudio A. ; De Souz, Antonio C Z ; Quintana, Victor H.
Author_Institution :
Dept. of Electr. & Comput. Eng., Waterloo Univ., Ont., Canada
Volume :
11
Issue :
3
fYear :
1996
fDate :
8/1/1996 12:00:00 AM
Firstpage :
1441
Lastpage :
1450
Abstract :
The paper proposes a new test function to be used in an existent performance index for detection of proximity to a static voltage collapse point. This test function is based on a reduction of the load flow Jacobian with respect to the critical bus of a system. The test function is compared with known singular values and eigenvalues indices, and with other previously proposed test functions. A thorough analysis of the similarities, advantages, and disadvantages of all these indices and test functions is presented. The techniques are tested and compared on the IEEE 300 bus test system, showing the effect of system characteristics and limits in these indices and functions
Keywords :
Jacobian matrices; eigenvalues and eigenfunctions; load flow; performance index; power system stability; IEEE 300 bus test system; eigenvalues indices; load flow Jacobian; performance index; performance indices; singular values; static voltage collapse proximity; test function; Bifurcation; Eigenvalues and eigenfunctions; Equations; Jacobian matrices; Load flow analysis; Power system modeling; Power system planning; Student members; System testing; Voltage;
fLanguage :
English
Journal_Title :
Power Systems, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8950
Type :
jour
DOI :
10.1109/59.535685
Filename :
535685
Link To Document :