DocumentCode :
136521
Title :
New wiring strategy and intelligent automatic test technology of 500kV transmission line protection devices
Author :
Siwei Yan ; Chunfeng Luo
Author_Institution :
Foshan Power Supply Bur., China Southern Power Grid Co. Ltd., Foshan, China
fYear :
2014
fDate :
Aug. 31 2014-Sept. 3 2014
Firstpage :
1
Lastpage :
3
Abstract :
A new handy periodical inspection method is introduced in connection with the problem that it takes long time and frequent wiring to accomplish traditional periodic inspection of 500 kV transmission line protection devices. The automatic test strategy of new handy periodical inspection method is analyzed according to typical configurations of 500 kV transmission line protection. An automatic test template is also developed independently with a well-known relay protection testing platform, which is applied to periodical inspection of several 500 kV transmission line protections in Foshan Power Supply Bureau. Application shows that the handy technique is valuable to be widely popularized for reducing the inadvertent mal-operation and improving the efficiency of periodical inspection.
Keywords :
inspection; power transmission protection; relay protection; wiring; Foshan Power Supply Bureau; intelligent automatic test technology; periodical inspection; relay protection testing platform; transmission line protection devices; voltage 500 kV; wiring strategy; Inspection; Power system protection; Power transmission lines; Protective relaying; Testing; Wiring; automatic test; relay protection; transmission line; wiring strategy;
fLanguage :
English