DocumentCode :
1378178
Title :
Probabilistic constrained load flow for optimizing generator reactive power resources
Author :
Hatziargyriou, N.D. ; Karakatsanis, T.S.
Author_Institution :
Dept. of Electr. & Comput. Eng., Nat. Tech. Univ. of Athens, Greece
Volume :
15
Issue :
2
fYear :
2000
fDate :
5/1/2000 12:00:00 AM
Firstpage :
687
Lastpage :
693
Abstract :
The generator reactive capability curve normally used in operation planning overestimates the reactive supply or absorption capabilities of the unit because it does not consider the operating conditions of the generator plant and of the electric power system. These are determined by the tap positions on the generator step-up and on the auxiliary unit transformer. This paper presents the application of probabilistic constrained load flow to optimal selection of these taps. It is shown that the technique proposed provides tap settings satisfying the reactive requirements for a whole range of operating conditions taking into account their probabilities of occurrence
Keywords :
load flow; power transformers; probability; reactive power; synchronous generators; auxiliary unit transformer; electric power system; generator reactive capability curve; generator reactive power resources optimisation; generator step-up; operating conditions; operation planning; optimal selection; probabilistic constrained load flow; synchronous generators; tap positions; tap settings; Absorption; Constraint optimization; Load flow; Power engineering computing; Power generation; Power system interconnection; Power system modeling; Power system planning; Power system simulation; Reactive power;
fLanguage :
English
Journal_Title :
Power Systems, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8950
Type :
jour
DOI :
10.1109/59.867160
Filename :
867160
Link To Document :
بازگشت