DocumentCode
1389210
Title
Effects of negative direct voltage pre-stressing on the breakdown of conductor-rod gaps under positive impulse voltages
Author
Allen, N.L. ; Gourgoulis, D.E. ; Mikropoulos, P.N. ; Stassinopoulos, C.A. ; Yakinthos, C.G.
Author_Institution
Dept. of Electr. Eng. & Electron., Univ. of Manchester Inst. of Sci. & Technol., UK
Volume
145
Issue
3
fYear
1998
fDate
5/1/1998 12:00:00 AM
Firstpage
105
Lastpage
109
Abstract
The sparkover of a 50 cm conductor rod gap under positive impulses is investigated when a pre-stressing negative direct voltage is applied to the rod. Under lightning impulses the pre-stress has a small effect on the breakdown voltage of the gap. For long-front impulses, a considerable increase in the dielectric strength of the gap can be observed. Several parameters affect this behaviour, like the value of the prestressing direct voltage, the diameter of the energised conductor, the position of the rod with regard to the conductor and the waveshape of the applied impulse
Keywords
air gaps; electric strength; humidity; lightning protection; probability; transients; breakdown probability; breakdown voltage; conductor-rod gaps; dielectric strength; energised conductor; humidity effect; lightning impulses; long-front impulses; negative direct voltage; negative direct voltage pre-stressing; positive impulse voltages; sparkover; waveshape;
fLanguage
English
Journal_Title
Science, Measurement and Technology, IEE Proceedings -
Publisher
iet
ISSN
1350-2344
Type
jour
DOI
10.1049/ip-smt:19981964