• DocumentCode
    1389210
  • Title

    Effects of negative direct voltage pre-stressing on the breakdown of conductor-rod gaps under positive impulse voltages

  • Author

    Allen, N.L. ; Gourgoulis, D.E. ; Mikropoulos, P.N. ; Stassinopoulos, C.A. ; Yakinthos, C.G.

  • Author_Institution
    Dept. of Electr. Eng. & Electron., Univ. of Manchester Inst. of Sci. & Technol., UK
  • Volume
    145
  • Issue
    3
  • fYear
    1998
  • fDate
    5/1/1998 12:00:00 AM
  • Firstpage
    105
  • Lastpage
    109
  • Abstract
    The sparkover of a 50 cm conductor rod gap under positive impulses is investigated when a pre-stressing negative direct voltage is applied to the rod. Under lightning impulses the pre-stress has a small effect on the breakdown voltage of the gap. For long-front impulses, a considerable increase in the dielectric strength of the gap can be observed. Several parameters affect this behaviour, like the value of the prestressing direct voltage, the diameter of the energised conductor, the position of the rod with regard to the conductor and the waveshape of the applied impulse
  • Keywords
    air gaps; electric strength; humidity; lightning protection; probability; transients; breakdown probability; breakdown voltage; conductor-rod gaps; dielectric strength; energised conductor; humidity effect; lightning impulses; long-front impulses; negative direct voltage; negative direct voltage pre-stressing; positive impulse voltages; sparkover; waveshape;
  • fLanguage
    English
  • Journal_Title
    Science, Measurement and Technology, IEE Proceedings -
  • Publisher
    iet
  • ISSN
    1350-2344
  • Type

    jour

  • DOI
    10.1049/ip-smt:19981964
  • Filename
    682028