DocumentCode :
1396824
Title :
Clapham static VAr compensator control retrofit
Author :
Stanley, E.B. ; Hedin, Ron ; Renz, Klaus ; Unterlass, Franz
Author_Institution :
Plains Electr., Albuquerque, NM, USA
Volume :
13
Issue :
3
fYear :
1998
fDate :
7/1/1998 12:00:00 AM
Firstpage :
889
Lastpage :
894
Abstract :
The performance of the Clapham SVC after a control retrofit is described. The replacement of an analogue with digital control was completed in 1995. The retrofit was accomplished well within the ten days of allotted shut down time. With the original control system, AC system voltage unbalance caused by untransposed lines had to be balanced by manual adjustment. The primary improvement provided with the new control is automatic and continuous voltage balancing
Keywords :
maintenance engineering; power system control; project engineering; reactive power control; static VAr compensators; voltage control; AC system voltage unbalance; USA; automatic continuous voltage balancing; digital control retrofit; performance; projects; static VAr compensator; AC motors; Automatic voltage control; Control systems; Impedance; Power harmonic filters; Reactive power; Resonance; Static VAr compensators; Transmission line measurements; Voltage control;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.686989