Overvoltages caused by unbalanced short circuits: Effect of amortisseur windings
Author :
Clarke, Edith ; Weygandt, C. N. ; Concordia, C.
Author_Institution :
The central station department, General Electric Company, Schenectady, N. Y.
Volume :
57
Issue :
8
fYear :
1938
Firstpage :
453
Lastpage :
468
Abstract :
IN CASE of unbalanced faults on power systems, the voltage on the unfaulted phase or phases may often reach very high values. There may be an overvoltage caused by the short circuit itself and a further overvoltage caused by the clearing of the fault. In the present paper only the first type will be discussed. These unfaulted phase overvoltages may vary widely with the type of fault, the system constants and arrangement, and the kinds of synchronous machines affected. However, in faults not involving ground the presence of overvoltages depends on the fact that the synchronous machines supplying the fault current are not electrically symmetric-rotor machines. Thus, these overvoltages may be largely eliminated or reduced by a properly designed amortisseur winding. Even in case of overvoltages caused by faults involving ground there is a considerable reduction with such an amortisseur winding.