Title :
Dynamic performance of a turboalternator utilising 3-term governor control and voltage regulation
Author_Institution :
Widnes Technical College, Electrical and Instrument Engineering Department, Widnes, UK
fDate :
2/1/1968 12:00:00 AM
Abstract :
Improved dynamic performance of a turboalternator may be achieved by the use of a 3-term prime-mover governor. Integral-of-speed and derivative-of-speed signals can be generated and combined with the conventional velocity signal, which then controls the input power. Transfer functions for the synchronous machine, turbine and governor mechanism are obtained from linear theory, and the frequency responses of the system operating with different prime-mover controller configurations are given on Bode diagrams. Interaction between the prime-mover steam-flow controller and the terminal-voltage exciter-field regulator is ascertained for a range of system operating conditions.
Keywords :
control engineering; synchronous generators; voltage control;
Journal_Title :
Electrical Engineers, Proceedings of the Institution of
DOI :
10.1049/piee.1968.0046