DocumentCode
1422337
Title
Use of dissipation factor for life consumption assessment and future life modeling of oil-filled high-voltage power cables
Author
Chmura, Lukasz ; Jin, Huifei ; Cichecki, Piotr ; Smit, Johan J. ; Gulski, Edward ; Vries, F.D.
Author_Institution
Delft Univ. of Technol., Delft, Netherlands
Volume
28
Issue
1
fYear
2012
Firstpage
27
Lastpage
37
Abstract
Tan δ measurements can be used to assess the condition of OF insulation in HV power cables. Data showing the behavior of tan δ as a function of temperature at constant electrical stress, and as a function of electrical stress at constant temperature, at different stages of degradation (or aging) are essential. By combining on-site and laboratory measurements, the remaining service lifetime of a cable can be estimated for various future loading levels using a model incorporating ground temperature, the age of the cable, and its loading history.
Keywords
life testing; oil filled cables; dissipation factor; electrical stress; life consumption assessment; oil-filled high-voltage power cables; Cable insulation; Degradation; High-voltage techniques; Load modeling; Oil filled cables; Power cables; dielectric loss; high-voltage cable; load modeling; oil-filled insulation; on-site diagnostics;
fLanguage
English
Journal_Title
Electrical Insulation Magazine, IEEE
Publisher
ieee
ISSN
0883-7554
Type
jour
DOI
10.1109/MEI.2012.6130529
Filename
6130529
Link To Document