• DocumentCode
    1422337
  • Title

    Use of dissipation factor for life consumption assessment and future life modeling of oil-filled high-voltage power cables

  • Author

    Chmura, Lukasz ; Jin, Huifei ; Cichecki, Piotr ; Smit, Johan J. ; Gulski, Edward ; Vries, F.D.

  • Author_Institution
    Delft Univ. of Technol., Delft, Netherlands
  • Volume
    28
  • Issue
    1
  • fYear
    2012
  • Firstpage
    27
  • Lastpage
    37
  • Abstract
    Tan δ measurements can be used to assess the condition of OF insulation in HV power cables. Data showing the behavior of tan δ as a function of temperature at constant electrical stress, and as a function of electrical stress at constant temperature, at different stages of degradation (or aging) are essential. By combining on-site and laboratory measurements, the remaining service lifetime of a cable can be estimated for various future loading levels using a model incorporating ground temperature, the age of the cable, and its loading history.
  • Keywords
    life testing; oil filled cables; dissipation factor; electrical stress; life consumption assessment; oil-filled high-voltage power cables; Cable insulation; Degradation; High-voltage techniques; Load modeling; Oil filled cables; Power cables; dielectric loss; high-voltage cable; load modeling; oil-filled insulation; on-site diagnostics;
  • fLanguage
    English
  • Journal_Title
    Electrical Insulation Magazine, IEEE
  • Publisher
    ieee
  • ISSN
    0883-7554
  • Type

    jour

  • DOI
    10.1109/MEI.2012.6130529
  • Filename
    6130529