Abstract
Transient analysis studies of the Hydro-Quebec 735-kV series-compensated network with the ideal switch representation for line circuit breakers exhibit the occurrence of abnormally delayed current-zero crossings under some fault conditions. The discovery of this phenomenon has triggered specific studies to verify the performance of existing air-blast circuit breakers and to draft the technical specifications of future SF6 gas circuit breakers
Keywords
arcs (electric); circuit-breaking arcs; power system analysis computing; power system protection; power system transients; power transmission lines; software packages; switchgear testing; 735 kV; SF6; SF6 gas circuit breakers; air-blast circuit breakers; delayed current-zero conditions; fault conditions; protection performance tests; series-compensated line circuit breakers; series-compensated transmission network; technical specifications; Capacitors; Circuit breakers; Circuit faults; Delay effects; EMTP; Electromagnetic transients; Sulfur hexafluoride; Switches; Transient analysis; Varistors;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/61.568245
Filename
568245
Link To Document