• DocumentCode
    1429965
  • Title

    Computation of eddy-current losses in cable sheaths and busbar enclosures

  • Author

    Heyda, P.G. ; Kitchie, G.E. ; Taylor, J.E.

  • Author_Institution
    British Insulated Callender´´s Cables Ltd., Central Research & Engineering Division, London, UK
  • Volume
    120
  • Issue
    4
  • fYear
    1973
  • fDate
    4/1/1973 12:00:00 AM
  • Firstpage
    447
  • Lastpage
    452
  • Abstract
    The usual method of calculating cable-sheath eddy-current losses gives satisfactory results for high-resistance sheaths but not for low-resistance sheaths. A method developed by Dwight for calculating this type of loss in unbonded busbar enclosures is applicable for low-resistance cable sheaths, but is not presented in a generalised form. A general method is given for the calculation of eddy-current losses in parallel and arbitrarily spaced thin tubes, some or all of which may contain other tubes. Two special cases are derived: one for three tubes equally spaced in triangular formation and the other for three tubes equally spaced lying in a plane. A table of loss factors has been prepared and deposited in the IEE Library. It covers wide ranges of two basic parameters, which enables it to be applied both to cable sheaths and busbar enclosures. Extracts from the table are given in the paper. It is shown that the finite wall thickness of the tubes can introduce appreciable additional losses, and an approximate formula for these is given.
  • Keywords
    busbars; cable sheathing; eddy current losses; busbar enclosures; cable sheaths; eddy current losses; finite wall thickness; loss factors; three tubes equally spaced;
  • fLanguage
    English
  • Journal_Title
    Electrical Engineers, Proceedings of the Institution of
  • Publisher
    iet
  • ISSN
    0020-3270
  • Type

    jour

  • DOI
    10.1049/piee.1973.0097
  • Filename
    5251042