• DocumentCode
    1430438
  • Title

    Reclosing relay for ring bus substations

  • Author

    Davidson, L. A. ; Hines, V. M.

  • Author_Institution
    Oklahoma Gas and Electric Company, Oklahoma City, Okla.
  • Volume
    80
  • Issue
    3
  • fYear
    1961
  • fDate
    3/1/1961 12:00:00 AM
  • Firstpage
    197
  • Lastpage
    197
  • Abstract
    RING buses as herein discussed are divided by circuit breakers into sections, each of which provides termination of a source or load. Each source or load may be connected to its section by a motor-operated air-break switch. Such a ring bus poses problems not encountered with a straight bus. A fault trips both circuit breakers of a section. When the circuit breakers trip, it is important that the ring be restored as rapidly as possible, since a true bus does not exist. If the ring should become open at another location, several problems may develop, depending on design. Generators can be isolated, the system split apart, relaying handicapped by separating zero-sequence sources, or loads dropped unnecessarily. It is important that a faulted line be isolated and the ring restored as rapidly as possible to shorten the vulnerable period. The best method of accomplishing this is to automatize the two circuit breakers and the air-break switch.
  • Keywords
    Assembly; Circuit breakers; Circuit faults; Relays; Switches; Switching circuits; Timing;
  • fLanguage
    English
  • Journal_Title
    Electrical Engineering
  • Publisher
    ieee
  • ISSN
    0095-9197
  • Type

    jour

  • DOI
    10.1109/EE.1961.6433684
  • Filename
    6433684