DocumentCode :
1456773
Title :
Energy stress on transmission line arresters considering the total lightning charge distribution
Author :
Stenström, L. ; Lundquist, J.
Author_Institution :
ABB Switchgear, Ludvika, Sweden
Volume :
14
Issue :
1
fYear :
1999
fDate :
1/1/1999 12:00:00 AM
Firstpage :
148
Lastpage :
151
Abstract :
Transmission line arresters may be subjected to high energy stresses caused by lightning. Calculations of energy stresses were carried out for a typical line arrester installation. Three line configurations with different degrees of shielding efficiency were used for the study. The primary statistical parameter was the charge of the flash, including multiple strokes. The effect of stroke current magnitude was also investigated. The calculated results were compared with energy stresses in standardized tests on surge arresters
Keywords :
arresters; electric charge; lightning; power overhead lines; power transmission protection; shielding; energy stress; flash charge; line configurations; multiple strokes; shielding efficiency; standardized tests; statistical parameter; stroke current magnitude; surge arresters; total lightning charge distribution; transmission line arresters; Arresters; Grounding; Lightning; Poles and towers; Power transmission lines; Stress; Substations; Surge protection; Transmission lines; Wires;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.736706
Filename :
736706