Modal Frequency Sensitivity for Power System Harmonic Resonance Analysis
Author :
Cui, Yu ; Wang, Xiaoyu
Author_Institution :
AltaLink, Calgary, AB, Canada
Volume :
27
Issue :
2
fYear :
2012
fDate :
4/1/2012 12:00:00 AM
Firstpage :
1010
Lastpage :
1017
Abstract :
Resonance-mode analysis is effective to determine the contributions of different network components to a resonance in power system harmonic studies. There are two forms of modal sensitivity in harmonic resonance mode analysis, that is, the modal impedance sensitivity and the modal frequency sensitivity. This paper presents a method to compute the modal frequency sensitivity index. The analysis results are compared with those obtained by using the modal impedance sensitivity index to clarify the differences and similarities between the two sensitivity indices. The comparison shows that these indices complement each other and should be used to jointly diagnose power system harmonic resonance problems.
Keywords :
power supply quality; power system harmonics; harmonic resonance mode analysis; modal frequency sensitivity index; modal impedance sensitivity; power system harmonic resonance analysis; Eigenvalues and eigenfunctions; Harmonic analysis; Impedance; Indexes; Power system harmonics; Resonant frequency; Sensitivity; Frequency sensitivity; harmonic resonance; modal analysis; power quality (PQ);
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/TPWRD.2012.2185520