Title :
A 735 kV shunt reactors automatic switching system for Hydro-Quebec network
Author :
Bernard, Serge ; Trudel, Gilles ; Scott, Guy
Author_Institution :
Hydro-Quebec, Montreal, Que., Canada
fDate :
11/1/1996 12:00:00 AM
Abstract :
Hydro-Quebec has undertaken a major program to upgrade the reliability of its transmission system. Much effort has been directed toward increasing the system´s capacity to withstand extreme contingencies, usually caused by multiple incidents or the successive tripping of transmission lines. In order to counter such events, Hydro-Quebec has adopted a defensive scheme. Based entirely on automatic action, this scheme will mainly rely on: a 735 kV shunt reactor switching system (called MAIS); a generation rejection and/or remote load-shedding system (called RPTC); and an underfrequency load-shedding system. The MAIS system, which is the subject of this paper, will be implemented in 22 substations and is required to control voltage on the system after a severe event. Each MAIS system, acting locally, is entirely independent and will close or trip shunt reactors in response to local conditions
Keywords :
load shedding; power system control; power system reliability; power system stability; reactors (electric); switching; switching substations; voltage control; 735 kV; Hydro-Quebec network; MAIS; RPTC; automatic switching system; extreme contingencies withstand; generation rejection system; oscillations modes; reliability; remote load-shedding system; shunt reactor closing; shunt reactor switching system; shunt reactor tripping; shunt reactors; stability; substations; switching control; transmission system; underfrequency load-shedding system; voltage control; voltage measurement; Automatic voltage control; Control systems; Inductors; Power system control; Power system dynamics; Power system reliability; Power systems; Shunt (electrical); Switching systems; Voltage control;
Journal_Title :
Power Systems, IEEE Transactions on