DocumentCode :
1473514
Title :
Application of identification methods for predicting the flashover voltage of contaminated insulators covered with ice
Author :
Sabri, Y. ; Farzaneh, M. ; Zhang, J.
Author_Institution :
Canada Res. on Atmos. Icing Eng. of Power Network (INGIVRE), Univ. du Quebec a Chicoutimi, Chicoutimi, QC, Canada
Volume :
17
Issue :
2
fYear :
2010
fDate :
4/1/2010 12:00:00 AM
Firstpage :
451
Lastpage :
457
Abstract :
The arc characteristics on contaminated insulator surfaces covered with ice were investigated. The arc constants (A, n), as well as the ac re-ignition parameters (K, b) were determined using a simplified cylindrical physical model. Based on identification methods, a new approach for calculating the residual voltage is introduced. These results will serve to extend the previous mathematical model developed at CIGELE for its application to predicting the flashover voltage of contaminated insulators covered with ice. The model was successfully applied to a five-unit IEEE standard insulator string, and the calculated results were in good agreement with the experiments.
Keywords :
flashover; insulator contamination; CIGELE; IEEE standard insulator string; ac re-ignition parameters; contaminated insulator surfaces; flashover voltage; identification methods; simplified cylindrical physical model; Dielectrics and electrical insulation; Environmentally friendly manufacturing techniques; Flashover; Ice surface; Mathematical model; Pollution; Power system modeling; Road transportation; Surface contamination; Voltage; Outdoor insulation, flashover phenomenon, electrical arc, identification methods, contaminated insulators covered with ice, flashover modeling.;
fLanguage :
English
Journal_Title :
Dielectrics and Electrical Insulation, IEEE Transactions on
Publisher :
ieee
ISSN :
1070-9878
Type :
jour
DOI :
10.1109/TDEI.2010.5448100
Filename :
5448100
Link To Document :