• DocumentCode
    1474610
  • Title

    Transient response of controlled rectifier circuits

  • Author

    Chin, P. T. ; Walter, G. E.

  • Author_Institution
    General Electric Company Schenectady, N. Y.
  • Volume
    64
  • Issue
    4
  • fYear
    1945
  • fDate
    4/1/1945 12:00:00 AM
  • Firstpage
    208
  • Lastpage
    214
  • Abstract
    Transients in circuits supplied by controlled rectifiers using gas or mercury-vapor-filled electron tubes are found analytically by an extended superposition method. Loads containing resistance, inductance, and a counter electromotive force are studied, and results are obtained for both rectification and inversion. Examples are based on the half-wave biphase rectifier, while the appendix contains an analysis of a p-phase rectifier. The assumptions include constant-circuit parameters, a fixed firing angle during transients, continuous load current, and no-leakage reactance in the supply transformer.
  • Keywords
    Electron tubes; Firing; Force; Inductance; Radiation detectors; Rectifiers; Transient analysis;
  • fLanguage
    English
  • Journal_Title
    Electrical Engineering
  • Publisher
    ieee
  • ISSN
    0095-9197
  • Type

    jour

  • DOI
    10.1109/EE.1945.6440977
  • Filename
    6440977