• DocumentCode
    1474910
  • Title

    Improved fault protection for rural distribution systems

  • Author

    Van Ryan, A.

  • Author_Institution
    Kyle Corporation, South Milwaukee, Wis.
  • Volume
    64
  • Issue
    5
  • fYear
    1945
  • fDate
    5/1/1945 12:00:00 AM
  • Firstpage
    261
  • Lastpage
    263
  • Abstract
    The use of automatic oil circuit reclosers on rural distribution lines has resulted in improved continuity of service as well as reduced maintenance cost. However, automatic circuit reclosers now in use are limited in application because of their inability to co-ordinate properly with fuses on the load side of the reclosers. An improved oil circuit recloser has been designed to incorporate the advantages of minimum time-delay opening on the first and second operations to clear all transient faults on the protected section, and greater time-delay opening on the third and fourth operations to allow the blowing of a sectionalizing or transformer fuse to isolate a permanent fault without causing a lockout of the recloser. A description is given of the design, operation, and advantages of this recloser which permits clearing of all transient line faults and isolates permanent faults by properly co-ordinating with sectionalizing fuses.
  • Keywords
    Circuit faults; Coils; Fuses; Pistons; Solenoids; Springs; Valves;
  • fLanguage
    English
  • Journal_Title
    Electrical Engineering
  • Publisher
    ieee
  • ISSN
    0095-9197
  • Type

    jour

  • DOI
    10.1109/EE.1945.6441022
  • Filename
    6441022