• DocumentCode
    1479869
  • Title

    Implementation of the CDA procedure in the EMTP

  • Author

    Lin, Jiming ; Marti, José R.

  • Author_Institution
    Electr. Power Res. Inst., Beijing, China
  • Volume
    5
  • Issue
    2
  • fYear
    1990
  • fDate
    5/1/1990 12:00:00 AM
  • Firstpage
    394
  • Lastpage
    402
  • Abstract
    The application of the critical damping adjustment (CDA) technique to some of the main equipment models in the DCG/EPRI version of EMTP is presented. The CDA procedure eliminates the numerical oscillations that can occur in transients simulations that use the trapezoidal rule of integration. The details of this implementation for linear elements, nonlinear reactors, frequency-dependent transmission lines, and synchronous machines are described. Simulation results involving these components are presented, showing the effectiveness of the procedure
  • Keywords
    damping; electromagnetic fields; power systems; transients; CDA; DCG/EPRI; EMTP; critical damping adjustment; electromagnetic transients program; frequency-dependent transmission lines; linear elements; nonlinear reactors; numerical oscillations; power systems; synchronous machines; transients simulations; Circuits; Damping; Difference equations; Differential equations; EMTP; Frequency dependence; History; Switches; Synchronous machines; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8950
  • Type

    jour

  • DOI
    10.1109/59.54545
  • Filename