• DocumentCode
    1485301
  • Title

    138-Kv pipe cable construction

  • Author

    Brookes, A. S. ; Starrs, T. E.

  • Author_Institution
    Public Service Electric & Gas Co., Newark, N. J.
  • Volume
    76
  • Issue
    10
  • fYear
    1957
  • Firstpage
    879
  • Lastpage
    879
  • Abstract
    IN 1956, Public Service Electric & Gas Co. constructed a 13-mile, 138-kv pipe cable from West Orange (N.J.) Switching station to a proposed switching station in Cranford. Special construction was required to permit this cable to be rated up from its normal value of 190 mva to 225 mva, to meet high terminal pressures resulting from a static head of 515 feet, and to anchor the cable on a steep grade near one end of the line.
  • Keywords
    Associate members; Cable insulation; Conductivity; Conductors; Switches; Thermal resistance;
  • fLanguage
    English
  • Journal_Title
    Electrical Engineering
  • Publisher
    ieee
  • ISSN
    0095-9197
  • Type

    jour

  • DOI
    10.1109/EE.1957.6442759
  • Filename
    6442759