• DocumentCode
    1490732
  • Title

    Application of dominant harmonic active filter system with 12 pulse nonlinear loads

  • Author

    Cheng, Po-Tai ; Bhattacharya, Subhashish ; Divan, Deepak M.

  • Author_Institution
    Dept. of Electr. & Comput. Eng., Wisconsin Univ., Madison, WI, USA
  • Volume
    14
  • Issue
    2
  • fYear
    1999
  • fDate
    4/1/1999 12:00:00 AM
  • Firstpage
    642
  • Lastpage
    647
  • Abstract
    Harmonic filtering is required for 12 pulse rectifier-utility interface to meet IEEE 519 harmonic current limits. Passive filter techniques employ tuned L-C filters at dominant 11th and 13th harmonic frequencies. However, they also require 5th and 7th tuned filters to avoid series and parallel resonance conditions. State of the art active filtering solutions require high bandwidth and relatively large rating PWM inverters for harmonic filtering of 12 pulse rectifier loads. Thus existing passive and active harmonic filtering solutions are not cost-effective for high power 12 pulse rectifier loads. Dominant harmonic active filter (DHAF) based on square-wave inverters is proposed to cost-effectively meet IEEE 519 harmonic current limits for 12 pulse rectifier loads. The proposed DHAF system employs square-wave inverters switching at 5th and 7th harmonic frequencies, which are transformer coupled in series with 11th and 13th passive filters respectively. The square-wave inverters are controlled to provide `harmonic isolation´ between the supply and load at 5th and 7th harmonic frequencies. The square-wave inverters are rated 1%-2% of the load kVA rating. The proposed DHAF system eliminates the need for large kVAR rated and bulky 5th and 7th passive filters, delivers superior harmonic filtering performance, and provides cost-effective harmonic filtering solution. Simulation results are given to validate the `harmonic isolation´ feature at 5th and 7th harmonic frequencies, and also demonstrate harmonic filtering required to meet IEEE 519 harmonic current limits
  • Keywords
    active filters; control system synthesis; invertors; load (electric); power conversion harmonics; power harmonic filters; rectifying circuits; voltage control; 12 pulse nonlinear loads; 12 pulse rectifier-utility interface; 5th harmonic frequency; 7th harmonic frequency; DC bus voltage control; IEEE 519 harmonic current limits; active filtering; controller design; dominant harmonic active filter system; feedback; feedforward; harmonic filtering; harmonic isolation; passive filter techniques; square-wave inverters; superior harmonic filtering performance; Active filters; Band pass filters; Filtering; Frequency; Passive filters; Power harmonic filters; Pulse inverters; Pulse transformers; Pulse width modulation inverters; Rectifiers;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.754112
  • Filename
    754112