DocumentCode :
1532770
Title :
Justification of Effective Reactive Power Reserves With Respect to a Particular Bus Using Linear Sensitivity
Author :
Choi, Y.H. ; Seo, S. ; Kang, S. ; Lee, B.
Author_Institution :
Dept. of Electr. Eng., Korea Univ., Seoul, South Korea
Volume :
26
Issue :
4
fYear :
2011
Firstpage :
2118
Lastpage :
2124
Abstract :
A constant reactive power (Q) reserve (CQR) is measured by the difference between the maximum reactive power generation and its current. However, all reactive power sources must not affect the entire power system when severe contingencies occur. Thus, generators must be evaluated as to whether or not they will have an impact on the maximum permissible loading of buses. This definition considers some generators to still have reactive power reserves when the system faces voltage collapse. This remaining reactive power reserve, although available, cannot be used in an arbitrary manner. This paper proposes the concept of an effective reactive power reserve and it is calculated on the basis of a sensitivity analysis. The computed reactive power reserve is analyzed using static and dynamic simulations in bulk power systems.
Keywords :
electric power generation; power system dynamic stability; reactive power; sensitivity analysis; bulk power system dynamic simulations; effective reactive power reserves; linear sensitivity analysis; maximum reactive power generation; reactive power sources; voltage collapse; Generators; Power system stability; Reactive power; Sensitivity; Stability criteria; Effective reactive power (Q) reserve (EQR); particular bus; reactive power reserve; sensitivity; voltage stability;
fLanguage :
English
Journal_Title :
Power Systems, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8950
Type :
jour
DOI :
10.1109/TPWRS.2011.2151212
Filename :
5783533
Link To Document :
بازگشت