• DocumentCode
    1544303
  • Title

    Pollution performance of 110 kV metal oxide arresters

  • Author

    Chrzan, Krystian ; Pohl, Zbigniew ; Grzybowski, Stan ; Köhler, Wolfgang

  • Author_Institution
    Dept. of Electr. Eng., Tech. Univ. Wroclaw, Poland
  • Volume
    12
  • Issue
    2
  • fYear
    1997
  • fDate
    4/1/1997 12:00:00 AM
  • Firstpage
    728
  • Lastpage
    733
  • Abstract
    Pollution test results of single-unit 110 kV metal oxide surge arresters with porcelain housing according to the solid layer and salt fog methods are presented. During 6 hours of testing, the internal and external charge and maximum temperature along the varistor column were measured. The formation of single stable dry bands on the housing was often observed especially during salt fog tests. In such cases, the varistor temperature can reach about 70°C. The simple electrical model of the arrester enabling calculations of voltages and currents as a function of arrester and pollution parameters is shown
  • Keywords
    arresters; charge measurement; electric breakdown; insulation testing; temperature measurement; thermal analysis; varistors; 110 kV; 6 h; 70 C; electrical model; external charge; insulation breakdown testing; internal charge; maximum temperature; metal-oxide surge arresters; pollution performance tests; porcelain housing; salt fog tests; solid layer tests; varistor column; Arresters; Charge measurement; Current measurement; Pollution; Porcelain; Solids; Surges; Temperature; Testing; Varistors;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.584358
  • Filename
    584358