DocumentCode
159223
Title
Transient recovery voltage risks and mitigation due to switching for oil sands fault reduction
Author
Pietramala, Peter C. ; Pak, Paul ; Shipp, David D. ; Dionise, Thomas J.
Author_Institution
Power Syst. Eng., Eaton Corp., Edmonton, AB, Canada
fYear
2014
fDate
8-10 Sept. 2014
Firstpage
443
Lastpage
450
Abstract
Current-limiting reactors are often used in applications where high fault currents encroach or exceed rated fault duties of downstream switchgear. Transient Recovery Voltages (TRV) that develop across the vacuum or SF6 interrupter contacts of the circuit breaker directly in series with the reactor during the interruption of reactor terminal faults can exceed TRV limits published for specific circuit breakers. This situation occurred in an Oil Sands application, where distribution system enhancements and expanded generation to meet process power and steam requirements resulted in overdutied medium voltage switchgear and required installation of a current limiting reactor. Using this case study from the Oil Sand application, this paper will examine transient program modeling techniques associated with reactor-limited fault current interruption and the subsequent TRV response that develops using electromagnetic transients program (EMTP) simulations. These TRV responses, subsequently, are compared to TRV envelopes established by harmonized IEC and IEEE Standards and, where available, manufacturer´s breaker lab testing results. In limited cases where the standards or published limits are exceeded, as did occur in this Oil Sands case study, TRV-reduction techniques and the associated practical solutions will be examined. Such practical solutions discussed in the paper include the application of surge capacitors, RC snubber circuits or uprating the breaker to a higher voltage rating.
Keywords
current limiting reactors; fault current limiters; oil circuit breakers; oil sands; vacuum circuit breakers; vacuum interrupters; EMTP simulations; RC snubber circuits; SF6 interrupter contacts; TRV envelopes; TRV-reduction techniques; circuit breaker; current-limiting reactor switching; distribution system enhancements; downstream switchgear; electromagnetic transients program simulations; expanded generation; oil sands fault reduction; overdutied medium voltage switchgear; reactor terminal faults; reactor-limited fault current interruption; surge capacitors; transient program modeling techniques; transient recovery voltage mitigation; transient recovery voltage risks; vacuum interrupter; Circuit breakers; Circuit faults; Fault currents; Generators; Inductors; Integrated circuit modeling; Transient analysis; TRV; current-limiting reactors; transient switching; transients; transients and surge protection;
fLanguage
English
Publisher
ieee
Conference_Titel
Petroleum and Chemical Industry Technical Conference (PCIC), 2014 IEEE
Conference_Location
San Francisco, CA
ISSN
0090-3507
Print_ISBN
978-1-4799-3054-8
Type
conf
DOI
10.1109/PCICon.2014.6961909
Filename
6961909
Link To Document