Low voltage ride through performance of a 4MVA synchronous generator - measurements and simulations
Author
Narayanan, Shrikanth ; Mebarki, Abdeslam ; Brown, Neil L.
Author_Institution
Cummins Generator Technol., Stamford, UK
fYear
2014
fDate
8-10 April 2014
Firstpage
1
Lastpage
3
Abstract
Complying with grid code requirements for low voltage ride through is a challenge for generator sets (GenSets). The generator experiences a short circuit at the beginning of the fault and then goes through severe recovery processes. It is shown that in some cases grid voltage recovery induces 25% higher peak current that the short circuit peak current for a 4MVA 1500rpm synchronous generator. Short circuit decrement tests are used to calibrate the Matlab model parameters and then extensive numbers of simulations are carried out to show the impact of LVRT on a large synchronous generator.
Keywords
calibration; fault diagnosis; power generation reliability; power grids; short-circuit currents; synchronous generators; GenSets; LVRT; Matlab model parameter calibration; apparent power 4 MVA; fault diagnosis; generator sets; grid code requirements; grid voltage recovery; low voltage ride through performance; short circuit decrement test; synchronous generator; Grid code; Low voltage ride through; Synchronous generators; generator;