    Monitoring of HV Generator Circuit Breaker Contact Ablation Based on Acoustic Emission

  • Author

    Ukil, Abhisek ; Zlatanski, Martin ; Hochlehnert, Moritz

  • Author_Institution
    ABB Corp. Res., Baden-Daettwil, Switzerland
  • Volume
    62
  • Issue
    10
  • fYear
    2013
  • fDate
    Oct. 2013
  • Firstpage
    2683
  • Lastpage
    2693
  • Abstract
    High-voltage (HV) generator circuit breaker (GCB) is a key protective element for isolating HV generators in case of faults, or operational reasons. GCB typically has a double contact system. During the breaking operation process of the GCB, at first the nominal contact opens; after a while, the arcing contact opens with a minimum time-elapse between the two operations. An arc ignites when the arcing contact opens. This arc should concern the arcing contact only because the nominal contact is not designed to withstand arcs. However, after each operation the arcing contact is slightly ablated because of the arc. The ablation due to arcing makes the contact shorter and shorter. Therefore, the time interval between the two opening operations also gets shorter. For proper operation of the GCB, a minimum time interval for the commutation of the current from the nominal contact system to the ablation contact system has to be assured. In this paper, a noninvasive direct ablation measurement method based on acoustic emission is presented. This is aimed at monitoring the delay in the time instant of the start of arcing contact touch as it gets shorter due to ablation, from the acoustic emission signals. Test results carried out on real breakers substantiate the proposed approach.
  • Keywords
    AC generators; acoustic measurement; arcs (electric); circuit breakers; electrical safety; ablation contact system; acoustic emission signal; arcing contact; breaking operation process; contact ablation monitoring; double contact system; high voltage generator circuit breaker; minimum time interval; nominal contact system; noninvasive direct ablation measurement method; opening operation; Ablation; CB diagnostics; HV breaker; accelerometer; arcing contact; condition monitoring; electrical contact erosion; online diagnostics; piezoelectric sensor; time delay measurement; vibration monitoring;
  • fLanguage
    English
  • Journal_Title
    Instrumentation and Measurement, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9456
  • Type

    jour

  • DOI
    10.1109/TIM.2013.2261612
  • Filename
    6549197