• DocumentCode
    160852
  • Title

    Design guidelines for safer low voltage distribution systems

  • Author

    Fox, Gary H.

  • Author_Institution
    Gen. Electr., Concord, CA, USA
  • fYear
    2014
  • fDate
    20-23 May 2014
  • Firstpage
    1
  • Lastpage
    10
  • Abstract
    Guidance is provided to designers of low voltage distribution systems on the maximum low voltage feeder rating of a unit substation that will allow the secondary main circuit breaker short time or instantaneous function to be sensitive enough to detect and trip on arcing currents and still coordinate with the feeder breaker settings. Recommendations are presented based on the transformer kVA rating, along with some variance for the primary source impedance and the instantaneous pickup tolerance of the feeder, based on it being either a molded case circuit breaker, insulated case circuit breaker or a low voltage power circuit breaker.
  • Keywords
    arcs (electric); circuit breakers; electrical safety; power distribution protection; arcing currents; circuit breaker; electrical safety; feeder breaker; instantaneous pickup tolerance; low voltage distribution systems; low voltage feeder rating; unit substation; IEEE standards; Indexes; Substations; Arc flash; coordination; electrical safety; power system protection; selectivity; transformers;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Industrial & Commercial Power Systems Tehcnical Conference (I&CPS), 2014 IEEE/IAS 50th
  • Conference_Location
    Fort Worth, TX
  • Print_ISBN
    978-1-4799-3308-2
  • Type

    conf

  • DOI
    10.1109/ICPS.2014.6839178
  • Filename
    6839178