Abstract :
Due to the design and layout of the electrolytic cell production plant, electrical safety is challenging. The cells, which are connected in a series circuit creating a large layout, are powered by a 200-500 volt DC source, which is intentionally ungrounded to provide personnel and equipment protection. Detection of the first ground connection of the electrolytic cell line is critical to ensure safety to personnel. Traditional methods of ground connection monitoring of a cell line, such as midpoint zero-volt detection, require constant analysis of data to determine if the first ground exists. This method can easily lead to human error, since the zero-volt location changes when cells are removed or added to the cell line. Also, the midpoint zero-volt method only functions when the cell line is energized, which makes troubleshooting not only a safety concern but also difficult. Moreover, if the ground connection occurs at the zero-volt location, there is no indication of the increased electrical hazard. Protection from electrical shocks and electrocution is safety critical and requires an instrument that continuously monitors the dynamic insulation resistance-to-ground of the entire cell line. The instrument must perform this vital safety function whether the cell line is energized or de-energized, so that finding the first ground quickly is easy and can be achieved without applying power to the cell line. Existing DC ground fault detection equipment, or insulation monitoring device, used in the mass transit and other industries has been adapted to accomplish this necessary ground fault detection in the electrolytic cell line; thereby, improving electrical safety in an electrolytic cell line.
Keywords :
cells (electric); earthing; electrical products industry; electrical safety; electrolytic devices; facilities layout; fault location; occupational safety; personnel; electrical hazard; electrical safety; electrical shocks; electrocution; electrolytic cell production plant layout; equipment protection; human error; midpoint zero-volt detection; personnel protection; series circuit; Electric potential; Insulation; Monitoring; Personnel; Power systems; Resistance; Safety;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Petroleum and Chemical Industry Conference (PCIC), 2010 Record of Conference Papers Industry Applications Society 57th Annual
Conference_Location :
San Antonio, TX
ISSN :
0090-3507
Print_ISBN :
978-1-4244-6800-3
Type :
conf
DOI :
10.1109/PCIC.2010.5666817
Filename :
5666817
Link To Document :
بازگشت