Title :
Evaluation of fault analysis tool under power swing and out-of-step conditions
Author :
Esmaeilian, A. ; Kezunovic, Mladen
Author_Institution :
Dept. of Electr. & Comput. Eng., Texas A&M Univ., College Station, TX, USA
Abstract :
Several major blackouts were caused by distance relay mis-operation. Distance relay mis-operation may occur following a large disturbance in the system causing power swing and out-of-step conditions. If an on-line fault analysis tool is able to detect power swing or out-of-step conditions and indicate mis-operation of relays, the operator may be notified to switch back the healthy transmission lines tripped due to relay mis-operation. A new automated fault analysis tool comprising fault detection, classification and location has been developed and its performance under various power swing and out-of-step conditions is reported. The test results indicate that the fault analysis tool performs better than distance relay under power swing and out of-step conditions and can be used as a tool to verify distance relay operation in practical circumstances. The simulations have been performed using IEEE118 bus test system modeled in ATP software.
Keywords :
control engineering computing; electricity supply industry deregulation; fault location; power system analysis computing; power system faults; power system stability; relays; ATP software; IEEE118 bus test system; automated fault analysis tool; distance relay mis-operation; fault classification; fault detection; fault location; online fault analysis tool evaluation; out-of-step conditions; power swing detection; power system deregulation; transmission lines; Circuit faults; Current measurement; Impedance; Protective relaying; Transmission line measurements; Voltage measurement; Fault diagnosis; out-of-step; power swing; power system faults; synchronized sampling;
Conference_Titel :
North American Power Symposium (NAPS), 2014
Conference_Location :
Pullman, WA
DOI :
10.1109/NAPS.2014.6965415