DocumentCode :
164695
Title :
The effect of real network phase disturbances on the calculation of IEC 61000-4-30 parameters
Author :
Rens, Johan ; de Kock, Jan ; van Wyk, Willie ; van Zyl, Jacobus
Author_Institution :
Sch. for Electr. & Electron. Eng., North-West Univ., Potchefstroom, South Africa
fYear :
2014
fDate :
25-28 May 2014
Firstpage :
303
Lastpage :
306
Abstract :
Real life network dynamic phenomena are used to demonstrate how the calculation of IEC 61000-4-30 parameters can be affected. The voltage frequency can change instantaneously at a point in the network due to a shift in the position of zero crosses when large reactive power changes occur. Pseudo voltage swells can be recorded and spectral leakage incurred. It is proposed that a 10/12-cycle block value for frequency is used in addition to the IEC 61000-4-30 10-second values.
Keywords :
IEC standards; power supply quality; reactive power; IEC 61000-4-30 parameter calculation; Pseudo voltage swell; network phase disturbance; reactive power change; spectral leakage; voltage frequency; zero crosses position; IEC standards; Phase locked loops; Power system dynamics; Time-frequency analysis; Voltage measurement; ½-cycle rms; 10/12 cycle block; Class A; IEC 61000-4-30; Power quality; SVC; asynchronous sampling; minimum standards in quality of supply; phase-locked loop; spectral leakage; voltage frequency;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Harmonics and Quality of Power (ICHQP), 2014 IEEE 16th International Conference on
Conference_Location :
Bucharest
Type :
conf
DOI :
10.1109/ICHQP.2014.6842886
Filename :
6842886
Link To Document :
بازگشت