    A new method to prevent distance protection from operating due to power swing

  • Author

    Pahlevan, Anahita ; Sadeh, Javad

  • Author_Institution
    Ferdowsi Univ. of Mashhad, Mashhad, Iran
  • Volume
    2
  • fYear
    2011
  • Firstpage
    1424
  • Lastpage
    1429
  • Abstract
    A power swing may cause unwanted tripping of the distance protection. The power swing blocking is a function commonly used to prevent the distance protection from operating during power swing. When a distance relay is blocked, it cannot react to faults anymore. This paper proposes a new method to prevent this protection from operating during power swing condition when no fault occurs. In this method, swings are removed from the voltage and current signals, using (d-q) frame, and then these signals are used in the impedance calculation of the distance relay. So, the distance protection is not blocked and can trip when a fault occurs. Simulation results are presented for a typical system using PSCAD software.
  • Keywords
    power system faults; power system protection; PSCAD software; current signals; d-q frame; distance protection prevention; impedance calculation; power swing blocking; power system faults; voltage signals; Automation; Frequency estimation; Impedance; Power system stability; Protective relaying; Time frequency analysis; Blocking prevention; Distance relay; Power swing blocking; Symmetrical fault;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Advanced Power System Automation and Protection (APAP), 2011 International Conference on
  • Conference_Location
    Beijing
  • Print_ISBN
    978-1-4244-9622-8
  • Type

    conf

  • DOI
    10.1109/APAP.2011.6180736
  • Filename
    6180736