Title
A new method to prevent distance protection from operating due to power swing
Author
Pahlevan, Anahita ; Sadeh, Javad
Author_Institution
Ferdowsi Univ. of Mashhad, Mashhad, Iran
Volume
2
fYear
2011
Firstpage
1424
Lastpage
1429
Abstract
A power swing may cause unwanted tripping of the distance protection. The power swing blocking is a function commonly used to prevent the distance protection from operating during power swing. When a distance relay is blocked, it cannot react to faults anymore. This paper proposes a new method to prevent this protection from operating during power swing condition when no fault occurs. In this method, swings are removed from the voltage and current signals, using (d-q) frame, and then these signals are used in the impedance calculation of the distance relay. So, the distance protection is not blocked and can trip when a fault occurs. Simulation results are presented for a typical system using PSCAD software.
Keywords
power system faults; power system protection; PSCAD software; current signals; d-q frame; distance protection prevention; impedance calculation; power swing blocking; power system faults; voltage signals; Automation; Frequency estimation; Impedance; Power system stability; Protective relaying; Time frequency analysis; Blocking prevention; Distance relay; Power swing blocking; Symmetrical fault;
fLanguage
English
Publisher
ieee
Conference_Titel
Advanced Power System Automation and Protection (APAP), 2011 International Conference on
Conference_Location
Beijing
Print_ISBN
978-1-4244-9622-8
Type
conf
DOI
10.1109/APAP.2011.6180736
Filename
6180736
Link To Document