DocumentCode :
172452
Title :
Improve the electrogeometric model by the analysis results of leader propagation model for transmission lines
Author :
Chijie Zhuang ; Rong Zeng ; Qian Li ; Hanbo Liu ; Zhanqing Yu ; Jinliang He
Author_Institution :
Dept. of Electr. Eng., Tsinghua Univ., Beijing, China
fYear :
2014
fDate :
11-18 Oct. 2014
Firstpage :
2020
Lastpage :
2023
Abstract :
Lightning shielding failure probability efficiency evaluation is important for transmission line design, especially for ultra-high voltage level. Traditional electrogeometric model (EGM) is not suitable for ultra-high voltage transmission lines because it neglects the upward leaders incepting from ground wires or power lines, while the lightning propagation model (LPM) works. The main contribution of this paper is to improve EGM by the analysis results of LPM. Besides adopting the concept of striking distance from traditional EGM, the concepts of upward leader length and its propagation angle, which describe the propagation process of upward leaders, were introduced. The formulae of improved EGM for a typical kind of 1000 kV transmission towers were obtained by numerical fitting of the calculation results of LPM. Results show the improved EGM coincides with LPM.
Keywords :
lightning protection; poles and towers; power transmission lines; EGM; LPM; electrogeometric model; ground wires; leader propagation model; lightning propagation model; power lines; transmission towers; ultra-high voltage transmission lines; voltage 1000 kV; Accuracy; Conductors; Lightning; Numerical models; Poles and towers; Power transmission lines; Wires; electrogeometric model; leader propagation model; lightning; striking distance; transmission line;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Lightning Protection (ICLP), 2014 International Conference o
Conference_Location :
Shanghai
Type :
conf
DOI :
10.1109/ICLP.2014.6973461