  • Abstract
    The main part of outages in the distribution grid caused by cable terminations and joints has been preceded by a period with internal partial discharges. As a tool for condition based maintenance, a method for on-line periodic discharge measurement based on ultrasound detection of signals emitted from the discharges has been developed. The method has a sensitivity in the 5-50 pC range depending on the design of the termination
  • Keywords
    XLPE insulation; acoustic emission testing; condition monitoring; electric connectors; insulation testing; maintenance engineering; partial discharge measurement; power cable insulation; power cable testing; quality control; ultrasonic applications; AE transducer; XLPE; acoustic method; condition based maintenance; distribution grid outages; field measurements; in-service periodic monitoring; internal partial discharges; medium voltage cable terminations; on-line periodic discharge measurement; quality control; ultrasound detection; Absorption; Acoustic sensors; Fault location; Frequency; Medium voltage; Monitoring; Probes; Quality control; Surface acoustic waves; Surface discharges;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Insulation, 1998. Conference Record of the 1998 IEEE International Symposium on
  • Conference_Location
    Arlington, VA
  • ISSN
    1089-084X
  • Print_ISBN
    0-7803-4927-X
  • Type

    conf

  • DOI
    10.1109/ELINSL.1998.704680
  • Filename
    704680