Abstract
1000kV/1000MVA UHV the scene of the transformer no-load test for the first time at home and abroad, in particular test voltage of 380V, Measuring mA current level, the corresponding test technology research is very difficult. In addition the transformer core remanence of the impact test results, effectively to demagnetizating UHV transformers is the key to the trial. In this study, using the method of parallel resonant 1000kV UHV to demagnetic transformer, through to the demagnetic exchange, the size of no-load current value is basically the same as the factory.The test achieved good results.
Keywords
power transformers; UHV transformers; transformer no-load test; ultra-high voltage transformer; voltage 1000 kV; voltage 380 V; Current measurement; Demagnetization; Remanence; Transformer cores; Voltage measurement; Voltage transformers; Windings;