DocumentCode
1757031
Title
Induction Motor Single-Phasing Performance Under Distribution Feeder Recloser Operations
Author
Agamloh, E.B. ; Peele, Scott ; Grappe, Joseph
Author_Institution
Adv. Energy Corp., Raleigh, NC, USA
Volume
50
Issue
2
fYear
2014
fDate
March-April 2014
Firstpage
1568
Lastpage
1576
Abstract
This paper presents an experimental investigation of the performance of induction motors subjected to single phasing on the primary side of a distribution transformer that feeds the motors. While single phasing caused by, for example, loss of fuse or bad contact is permanent in nature, that caused by recloser operation is momentary and is the focus of this paper. Several motors and transformer connections were used to investigate the effects of the momentary interruptions of a phase on the performance of the induction motors. The conditions under which the motors are able to ride through the single phasing are presented and discussed.
Keywords
induction motors; transformers; distribution feeder recloser operations; distribution transformer; induction motor single-phasing performance; Circuit faults; Fuses; Heating; Induction motors; Phase transformers; Torque; Windings; Induction motors; reclosers; single phasing;
fLanguage
English
Journal_Title
Industry Applications, IEEE Transactions on
Publisher
ieee
ISSN
0093-9994
Type
jour
DOI
10.1109/TIA.2013.2279188
Filename
6583997
Link To Document