• DocumentCode
    1780174
  • Title

    Effect of Kraft Paper barriers on bridging in contaminated transformer oil

  • Author

    Mahmud, S. ; Golosnoy, I. ; Chen, Gang ; Wilson, G. ; Jarman, P.

  • Author_Institution
    Electron. & Comput. Sci., Univ. of Southampton, Southampton, UK
  • fYear
    2014
  • fDate
    19-22 Oct. 2014
  • Firstpage
    110
  • Lastpage
    113
  • Abstract
    The paper investigates effects of Kraft Paper to prevent bridging in pressboard fibre contaminated transformer oil. There are three different configuration of Kraft paper tested. These are 1) covered electrode with loose bond, 2) tight bond and 3) bare electrode with a paper barrier in the middle. There were no bridges formed with loosely bonded tests with DC electric fields. For the other two cases, there was always a complete bridge formed.
  • Keywords
    contamination; paper; power transformer insulation; transformer oil; bare electrode; covered electrode; kraft paper barriers; paper barrier; pressboard fibre contaminated transformer oil; Bridge circuits; Electric fields; Electrodes; Oil insulation; Optical fibers; Power transformer insulation; Coulomb force; bridging; charge transportation; dielectrophoresis; transformer oil;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Insulation and Dielectric Phenomena (CEIDP), 2014 IEEE Conference on
  • Conference_Location
    Des Moines, IA
  • Type

    conf

  • DOI
    10.1109/CEIDP.2014.6995865
  • Filename
    6995865