Title :
Improved architecture for Profinet IRT devices
Author :
Felser, C. ; Felser, Max ; Kaghazchi, Hamed
Abstract :
This paper deals with Real-Time applications based on Profinet IO Real-Time Class 3. The industrial automation in some cases requires the precision of IO data timing well below the delivered cycle time on the bus. When using the Isochronous Real-Time protocol of Profinet, one single predefined time within a cycle time can be chosen for the inputs- and outputs. The work presented here, shows how the architecture of a Profinet device can be improved. The user can define the time of an input or output within the given time slot with an accuracy of 65 nanoseconds. Furthermore the feasibility of the proposed design is proven with several measurements and simulations.
Keywords :
factory automation; local area networks; protocols; real-time systems; IO data timing; Profinet IO Real-Time Class 3; Profinet IRT device architecture; Profinet device; cycle time; industrial automation; isochronous real-time protocol; real-time application; time slot;
Conference_Titel :
Emerging Technologies & Factory Automation (ETFA), 2012 IEEE 17th Conference on
Conference_Location :
Krakow
Print_ISBN :
978-1-4673-4735-8
Electronic_ISBN :
1946-0740
DOI :
10.1109/ETFA.2012.6489562