  • Abstract
    Earthing has been identified as one of the main issues pertaining to an intentional islanding. The issue is significance for any rotating type of DG operating in Networks a distribution networks. The problem arises for a system adopting single point earthing when a DG is disconnected from the grid and continues to supply power to an islanded system that does not contain an earth connection. Therefore, this paper describes a study that considers the earthing arrangement for a single point, low impedance earthed distribution network with a particular emphasis on the earthing requirements when a section of the network is operating islanded. The study is evaluated on a simulated network constructed using the PSCAD/EMTDC simulator. The study showed that an appropriate operating procedure for islanded operation is required to ensure continuity of the earth connection in the islanded system.
  • Keywords
    distributed power generation; distribution networks; earthing; DG; PSCAD/EMTDC simulator; UK radial distribution; earthing strategy; islanded operation; low impedance earthed distribution network; single point earthing; EMTDC; Earth; Grounding; Hazards; Health and safety; PSCAD; Power supplies; Power system interconnection; Power system reliability; Voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Universities Power Engineering Conference (UPEC), 2009 Proceedings of the 44th International
  • Conference_Location
    Glasgow
  • Print_ISBN
    978-1-4244-6823-2
  • Type

    conf

  • Filename
    5429581