Abstract
In substations, shielded cables are widely used to reduce transient electromagnetic interference to the relay and control equipments due to the switch operation. Both the transfer impedance and transfer admittance are quantities for expressing numerically the mechanism that allows the passage of electromagnetic energy across the cable shield. Theoretical models to compute both the quantities often rely on simplifying assumptions. This, together with the fact that the transfer impedance and admittance can vary considerably between cable samples of the same type, means that measurements become necessary. In this paper, based on the transmission line theory we present a simple method to measure the transfer impedance and admittance of shielded cable in magnitude as well as in phase over the frequency range (0.1 MHz-10 MHz) which covers the main interference frequencies in power system. To illustrate this method a coaxial cable with a braided shield has been measured and compared with the existing method. As an application, the proposed method is used to predict the induced voltage and current on the shielded cable due to the switch operation in substation
Keywords
cable shielding; electric admittance; electromagnetic interference; electromagnetic shielding; matrix algebra; power cables; substations; transmission line theory; complex transfer impedance; electromagnetic energy; induced voltage; interference frequencies; power system; reduce transient electromagnetic interference; shielded cable admittance; substations; transmission line theory; Admittance measurement; Cable shielding; Electromagnetic measurements; Frequency; Impedance measurement; Power cables; Power system transients; Substations; Switches; Transmission line measurements; Electromagnetic interference in substations; measurement; shielded cable; transfer impedance and admittance;
fLanguage
English
Publisher
ieee
Conference_Titel
Electromagnetic Compatibility, 2006. EMC-Zurich 2006. 17th International Zurich Symposium on
Conference_Location
Singapore
Print_ISBN
3-9522990-3-0
Type
conf
DOI
10.1109/EMCZUR.2006.215018
Filename
1629708
Link To Document