DocumentCode :
1923730
Title :
Smart high voltage circuit breaker in overhead power lines for smart grid applications
Author :
Pasdar, A.M. ; Sozer, Yilmaz
fYear :
2013
fDate :
15-19 Sept. 2013
Firstpage :
1118
Lastpage :
1123
Abstract :
Fault detection and protection is a major concern in electric transmission and distribution network. Faults having high impedance on an energized network are difficult to capture and pose great threat for safety and security. Smart circuit breaker is presented for detecting a fault during the real time operation of the power system. The proposed method monitors the high frequency impedance of the grid in a real time which can operate in both energized and de-energized conditions. In order to measure the impedance, circuit breaker injects high frequency signal into the line. Injected signal is blocked by a LC line trapper at the substation side and by an active blocker at the opposing end of the desired segment. Relative change in the measured impedance is a reference to detect the presence of the high impedance fault. The validity of the proposed method is verified with simulations.
Keywords :
circuit breakers; fault diagnosis; power grids; power overhead lines; power transmission faults; power transmission protection; LC line trapper; active blocker; deenergized condition; fault detection; fault protection; high frequency impedance; high impedance fault; overhead power lines; smart grid application; smart high voltage circuit breaker; Circuit breakers; Circuit faults; Conductors; Frequency measurement; Impedance; Impedance measurement; Substations; Smart circuit breaker; active signal blocker; high frequency signal injection to grid; smart grid; smart protective device;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Energy Conversion Congress and Exposition (ECCE), 2013 IEEE
Conference_Location :
Denver, CO
Type :
conf
DOI :
10.1109/ECCE.2013.6646830
Filename :
6646830
Link To Document :
بازگشت