Temporary overvoltages in the Vietnam 500 kV network
Author :
Lam-Du, S. ; Tran-Quoc, T. ; Feuillet, R. ; Sabonnadiere, J.C. ; Nguyen, Quang
Author_Institution :
HCM City Electr. Co., Ho Chi-Minh
Volume :
1
fYear :
1998
fDate :
3-5 Mar 1998
Firstpage :
275
Abstract :
This paper investigates the temporary overvoltages (TOV) in the Vietnam 500 kV system. The modeling of transformers, lines and other elements in the Vietnam system is presented. Several events that can produce high TOV levels, such as three-phase load rejections, single-phase opening with the outage of a shunt reactor, the bypassing of a series capacitor or the disconnecting of a transformer, etc., are examined with the help of the EMTP program. Finally, the methods of limiting the magnitude and duration of TOV levels applied to equipment are presented
Keywords :
overvoltage; power system transients; power transformers; 500 kV; EMTP program; Vietnam system; hysteresis; line modeling; saturation; series capacitor bypass; shunt reactor outage; single-phase opening; surge arrester; temporary overvoltages; three-phase load rejections; transformer disconnection; transformer modeling; Arresters; Capacitors; Cities and towns; Hysteresis; Inductors; Intelligent networks; Power transmission lines; Shunt (electrical); Surge protection; Transformers;