Abstract :
Laboratory investigation of the effect of harmonics on induction watthour meters is presented. The study is focused on the effects of harmonics when they are injected from the source side and from the load side. The studies indicate that the watthour meters give negative error when the frequency is injected from the source side. Moreover, higher negative error was observed for even-order harmonics. An insignificant error was observed when similar studies were repeated from the customer side
Keywords :
harmonics; measurement errors; watthour meters; even-order harmonics; induction watthour meters; laboratory investigations; load side; negative error; source side; watthour meters; Current measurement; Distortion measurement; Energy measurement; Frequency; Laboratories; Magnetic analysis; Mathematical model; Power measurement; Voltage; Watthour meters;