• DocumentCode
    1963275
  • Title

    Effect of harmonics on watthour meters-laboratory investigations

  • Author

    Ogundare, Ayodeji A. ; Kumar, Aahok ; Collis, Ward ; Stevens, John

  • Author_Institution
    Dept. of Electr. Eng., North Carolina A&T Univ., Greensboro, NC, USA
  • fYear
    1989
  • fDate
    14-16 Aug 1989
  • Firstpage
    278
  • Abstract
    Laboratory investigation of the effect of harmonics on induction watthour meters is presented. The study is focused on the effects of harmonics when they are injected from the source side and from the load side. The studies indicate that the watthour meters give negative error when the frequency is injected from the source side. Moreover, higher negative error was observed for even-order harmonics. An insignificant error was observed when similar studies were repeated from the customer side
  • Keywords
    harmonics; measurement errors; watthour meters; even-order harmonics; induction watthour meters; laboratory investigations; load side; negative error; source side; watthour meters; Current measurement; Distortion measurement; Energy measurement; Frequency; Laboratories; Magnetic analysis; Mathematical model; Power measurement; Voltage; Watthour meters;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Circuits and Systems, 1989., Proceedings of the 32nd Midwest Symposium on
  • Conference_Location
    Champaign, IL
  • Type

    conf

  • DOI
    10.1109/MWSCAS.1989.101846
  • Filename