DocumentCode :
1966716
Title :
On the use of S-transform for fault feeder detection based on two phase currents in distribution power systems
Author :
Shu Hongchun ; Xu, Wang ; Xincui, Tian ; Qianjin, Wu ; Peng Shixin
Author_Institution :
Fac. of Electr. Eng., Kunming Univ. of Sci. & Technol., Kunming, China
Volume :
2
fYear :
2010
fDate :
10-11 July 2010
Firstpage :
282
Lastpage :
287
Abstract :
The paper presents a procedure for fault feeder detection in distribution power systems, based on the use of the amplitude-time and argument-time by S-transform of the zero-module bus voltage and two phase currents transients associated with the fault-originated traveling waves. The analysis carried out shows that the argument of currents have difference 180° between fault feeder and sound feeders at fault-originated which make fault feeder detectible. A large number of simulation results demonstrate the feasibility and validity of the procedure.
Keywords :
fault diagnosis; power distribution faults; time-frequency analysis; wavelet transforms; S-transform; amplitude-time use; argument-time use; distribution power system; fault feeder detection; fault-originated traveling waves; sound feeder; two phase current; two phase current transient; zero-module bus voltage; Current measurement; Transforms; γmodule currents; Argument; Fault feeder detection; Power distribution systems; S-transform;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Industrial and Information Systems (IIS), 2010 2nd International Conference on
Conference_Location :
Dalian
Print_ISBN :
978-1-4244-7860-6
Type :
conf
DOI :
10.1109/INDUSIS.2010.5565706
Filename :
5565706
Link To Document :