DocumentCode :
1975028
Title :
Effect of arc time on the current breaking capability of vacuum interrupters
Author :
Taylor, E.D. ; Lawall, A. ; Genzmer, J. ; Heydenreich, T.
Author_Institution :
Siemens AG, Berlin, Germany
fYear :
2013
fDate :
20-23 Oct. 2013
Firstpage :
1
Lastpage :
4
Abstract :
Vacuum interrupters on medium voltage power systems need to interrupt short-circuit currents over a wide range of arc times. Synthetic testing allows the careful study of the interruption performance over arc times ranging from 0 to 13.3ms for a 50Hz system. Comparing the interruption performance as a function of arc time observed in single- and three-phase direct testing and single-phase synthetic testing gives good agreement. This agreement extends over different rating points, different contact designs, and different arc control methods. Additional tests compared synthetic tests with and without re-ignition for arc times greater than 10ms.
Keywords :
arcs (electric); electric ignition; power systems; short-circuit currents; vacuum interrupters; arc time effect; current breaking capability; frequency 50 Hz; medium voltage power system; short-circuit current interruption; single-phase direct testing; single-phase synthetic testing; three-phase direct testing; time 0 ms to 13.3 ms; vacuum interrupter; Interrupters; Presses; Switches; Time-frequency analysis; Vacuum arcs;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electric Power Equipment - Switching Technology (ICEPE-ST), 2013 2nd International Conference on
Conference_Location :
Matsue
Type :
conf
DOI :
10.1109/ICEPE-ST.2013.6804288
Filename :
6804288
Link To Document :
بازگشت